Choosing the correct diesel generator capacity is essential for reliable power supply, efficient operation, and cost-effective investment. Whether you need backup power for a commercial building, a construction site, or a large industrial facility, understanding generator kVA ratings can help you make the right purchasing decision.

At Ultra Power Generators FZC, located in SAIF Zone, Sharjah, UAE, we assemble and supply diesel generator solutions for commercial and industrial applications, including Perkins-powered generator , Cummins-powered generator, John Deere-powered generator,  and containerized power solutions.

This guide explains how to calculate generator capacity, understand kVA and kW, and identify important factors before purchasing a diesel generator in the UAE.

What Is kVA in a Diesel Generator?

kVA stands for kilovolt-amperes. It measures the apparent electrical power supplied by a generator.

Diesel generators are commonly rated in kVA because their output must accommodate both active and reactive power requirements.

The two important measurements are:

  • kVA (kilovolt-amperes): Apparent power.
  • kW (kilowatts): Real power available to perform useful work.

The relationship between them is determined by the electrical system’s power factor.

How to Convert kVA to kW

The basic formula is:

kW = kVA × Power Factor

For example, if a generator is rated at 100 kVA with a power factor of 0.8:

100 kVA × 0.8 = 80 kW

This means the generator has a rated real power output of 80 kW at the stated power factor, subject to its operating rating and conditions.

Similarly:

kVA = kW ÷ Power Factor

For a 200 kW load at 0.8 power factor:

200 ÷ 0.8 = 250 kVA

However, this is only a preliminary calculation. Actual generator sizing must also consider starting currents, operating conditions, and the generator manufacturer’s specifications.

Diesel Generator kVA to kW Conversion Chart

The following table shows common generator ratings at an assumed power factor of 0.8.

Generator Capacity Equivalent kW
5 kVA 4 kW
10 kVA 8 kW
20 kVA 16 kW
45 kVA 36 kW
50 kVA 40 kW
100 kVA 80 kW
150 kVA 120 kW
200 kVA 160 kW
250 kVA 200 kW
500 kVA 400 kW
750 kVA 600 kW
1000 kVA 800 kW

Note: These are mathematical conversions, not a list of confirmed available UPG models. Actual generator output depends on the specific model, rated power factor, operating duty, and site conditions.

How to Choose the Right Diesel Generator kVA

Step 1: Calculate Your Total Electrical Load

Start by listing all the equipment that the generator must power.

Typical electrical loads may include:

  • Air conditioning and ventilation systems
  • Industrial machinery and electric motors
  • Lighting and office equipment
  • Water pumps and compressors
  • Construction equipment
  • IT systems and essential electrical services

Record the rated power consumption of each item in kW or watts.

If an appliance is rated in watts:

kW = Watts ÷ 1000

For example, a 5000-watt load is equivalent to 5 kW.

Remember that not all connected equipment necessarily operates simultaneously. Determine the realistic maximum simultaneous demand rather than simply adding every nameplate rating.

Step 2: Convert Your Required kW into kVA

Once you know the estimated simultaneous electrical demand, calculate the apparent power requirement using the expected load power factor.

For example, assume a facility has a maximum simultaneous load of 120 kW and an overall power factor of 0.8.

120 kW ÷ 0.8 = 150 kVA

This gives a preliminary apparent-power requirement of 150 kVA.

It does not automatically mean that a 150 kVA generator will be suitable. Motor starting loads, voltage dip limits, temperature, and other factors must still be assessed.

Step 3: Consider Motor Starting Requirements

Electrical motors can draw substantially more current during startup than during normal operation.

Equipment such as compressors, pumps, and large air-conditioning systems may create significant starting demand.

A generator that supports the normal running load may still struggle when a large motor starts.

Generator sizing should therefore consider:

  • Motor starting method
  • Starting current and power factor
  • Acceptable voltage and frequency dips
  • Whether multiple motors start simultaneously
  • Variable frequency drives or soft starters

For installations with significant motor loads, request a technical sizing assessment.

Step 4: Allow for Future Expansion

If your business plans to install additional equipment, consider future electrical demand when selecting a generator.

A reasonable capacity allowance may help accommodate growth, but excessive oversizing can increase costs and cause inefficient operation at low loads.

The appropriate allowance should be determined by the expected future load and the generator manufacturer’s operating recommendations.

Step 5: Consider UAE Climate and Installation Conditions

Diesel generators operating in the UAE may face high ambient temperatures, dust, and demanding outdoor conditions.

These conditions can influence engine performance, cooling requirements, and equipment reliability.

Before selecting a generator, confirm:

  • Ambient temperature rating
  • Engine and alternator derating requirements
  • Ventilation and cooling arrangements
  • Dust protection
  • Installation altitude
  • Enclosure suitability

A generator’s standard rating may require adjustment under certain site conditions.

Step 6: Choose Between Standby and Prime Power

Generator capacity is also affected by the intended operating duty.

Standby Power: Generally used when the normal utility supply fails, within the manufacturer’s specified operating limitations.

Prime Power: Intended for applications requiring extended operation with variable loads, subject to the manufacturer’s rating definitions and conditions.

A generator’s standby rating and prime rating may differ. Always confirm which rating is stated on the quotation and datasheet.

What Generator Size Do Different Businesses Need?

There is no single generator capacity suitable for every business.

A small commercial facility may have relatively modest backup power requirements, while an industrial facility with heavy machinery may require hundreds of kVA.

Application Main Sizing Considerations
Small office or retail shop Lighting, air conditioning, IT equipment
Restaurant or commercial kitchen Refrigeration, ventilation, cooking equipment
Construction site Machinery, welding equipment, pumps, starting currents
Warehouse Lighting, ventilation, material-handling equipment
Manufacturing facility Industrial motors, machinery, compressors
Large industrial project High electrical demand, load sequencing, redundancy

The correct generator size must be calculated from actual electrical loads, not estimated from the building or business type alone.

Example: How to Calculate Generator Capacity for a Business

Consider a hypothetical commercial facility with the following maximum simultaneous loads:

Electrical Equipment Running Load
Air conditioning 40 kW
Lighting 10 kW
Office and IT equipment 15 kW
Pumps and auxiliary equipment 15 kW
Total 80 kW

Assuming a combined power factor of 0.8:

80 kW ÷ 0.8 = 100 kVA

The preliminary requirement is 100 kVA.

If a 20% planning allowance is applied to both the kW and kVA demand, the preliminary values become:

  • Real power requirement: 96 kW
  • Apparent power requirement: 120 kVA

This is an illustrative planning calculation, not a final generator selection.

The actual generator must be checked for motor starting, step-load acceptance, environmental derating, power quality, and the applicable prime or standby rating.

Why Proper Diesel Generator Sizing Matters

Choosing an appropriately sized diesel generator can help businesses:

  • Reduce the risk of overload and power interruptions
  • Support stable operation of connected equipment
  • Avoid unnecessary initial investment
  • Improve operating efficiency
  • Allow for planned future electrical demand
  • Support long-term equipment reliability

Both undersizing and excessive oversizing can create operational problems.

A proper technical assessment helps balance performance, reliability, and cost.

Diesel Generator Solutions from Ultra Power Generators UAE

Ultra Power Generators FZC provides diesel generator assembly and supply solutions for commercial and industrial applications.

Our product range includes Perkins-powered diesel generators and containerized generator solutions for projects requiring larger power systems.

We can assist customers in reviewing generator requirements, including:

  • Required kVA and kW capacity
  • Standby or prime power application
  • Engine and alternator specifications
  • Site operating conditions
  • Generator enclosure requirements
  • Available generator configurations

Our team can discuss suitable generator models based on your project requirements and applicable technical specifications.

Frequently Asked Questions About Generator kVA

1. What does kVA mean in a diesel generator?

kVA means kilovolt-amperes. It measures apparent electrical power and is commonly used to express a generator’s rated capacity.

2. How many kW is a 100 kVA generator?

At a rated power factor of 0.8, a 100 kVA generator corresponds to 80 kW of real power. The applicable rating and operating conditions must also be considered.

3. How do I calculate the generator kVA required for my business?

Determine the maximum simultaneous electrical load in kW, divide it by the expected overall power factor, and then evaluate motor starting, future expansion, environmental conditions, and operating duty.

4. Is a 50 kVA generator enough for a small business?

It depends on the business’s actual electrical demand. At a power factor of 0.8, 50 kVA corresponds to 40 kW, but starting loads and other operating factors may require a different generator size.

5. What happens if a diesel generator is too small?

An undersized generator may experience overload, excessive voltage or frequency drops, protective shutdowns, or difficulty starting large motors.

6. Is a bigger generator always better?

No. An unnecessarily oversized generator may cost more and operate inefficiently at low loads. Correct sizing is preferable to simply choosing the largest available unit.

7. What is the difference between prime and standby kVA?

Prime and standby kVA refer to different operating duty ratings. The permissible operating conditions and limitations are defined by the generator or engine manufacturer.

8. Can Ultra Power Generators help me select the correct generator capacity?

Yes. Customers can contact Ultra Power Generators FZC to discuss their electrical load requirements, operating conditions, and suitable diesel generator configurations.

Request a Diesel Generator Quotation in UAE

Not sure whether your project needs a 50 kVA, 100 kVA, 500 kVA, or 1000 kVA generator?

Contact Ultra Power Generators FZC to discuss your power requirements and available generator solutions.

For a more accurate recommendation, please provide:

  • Required power load in kW or kVA
  • Type of equipment to be powered
  • Standby or prime power requirement
  • Voltage and frequency requirements
  • Installation location
  • Expected daily operating hours